Outside Oil Tank Rules
|
|
1. |
Oil supply tanks shall not be installed on wood or other
combustible surfaces or supports.
|
| 2. |
Outside oil supply tanks of 350 gallons or less shall be
supported in accordance with Rules 3 and 4.
|
| 3. |
A horizontal oil supply tank shall be mounted on steel pipe
legs, not exceeding twelve (12) inches in height with floor
flanges at the base of the steel legs and be supported by four
(4), 4 x 8 x 16 inch concrete blocks, or a one (1) piece
reinforced concrete pad not smaller than the tank dimensions.
The four (4) blocks or the pad shall rest on a firm subgrade
consisting of a bed of compacted, well draining gravel (6 inch
minimum), crushed stone (6 inch minimum), or some other subgrade
approved by the Board. See Figure 12(a).
There must be a minimum of 4” of clearance under the tank from
any surface. See Figure 12(a)).
|
| 4. |
An upright or vertical tank shall be mounted on steel pipe
legs not exceeding twelve (12) inches in height, with floor
flanges at the base of the steel leg, and supported by a
reinforced concrete pad at least three (3) inches thick. The
pad's width and length shall not be smaller than the tank
dimensions. The pad shall be of one (1) piece construction. The
pad shall rest on a bed of compacted, well draining gravel (6
inches minimum), crushed stone (6 inches minimum), or some other
subgrade approved by the Board. There must be a minimum of 4
inches of clearance under the tank from any surface. See
Figure 12(b)).
|
|
5. |
When installing a vertical fuel oil tank in a listed
secondary containment system, the four (4) inch clearance
requirement from the bottom of the tank to any surface may be
reduced to a minimum of one (1) inch.
|
| 6. |
The leg brackets welded on the tank shall not
be considered a leg and may not be used to rest on the side of
the reinforced concrete pad or concrete blocks.
|
| |
|
|
| |
|
|
| |
6. |
The leg brackets welded on the tank shall not be considered a
leg and may not be used to rest on the side of the reinforced
concrete pad or concrete blocks.
|
| |
7. |
When a reinforced concrete pad is fabricated on-site, the
legs of the supply tanks shall not be embedded as part of the
pad.
|
| |
8. |
In all installations, the pipe flanges must be in direct
contact with a reinforced concrete pad or concrete blocks.
|
| |
9. |
Tanks must be disposed of in accordance with the Department
of Environmental Protections Rules. Used, underground, oil
storage tanks are prohibited from use for aboveground supply of
oil except where a Maine registered engineer certifies that the
tank meets the requirements of UL 142 and NFPA 30.
|
| |
10. |
Outside tanks and piping must be located such that they are
not subject to falling snow or ice. To meet this requirement,
the tank and outdoor piping must be installed with a protective
cover over the tank valve, oil filter, and any piping which is
either without structural support or not attached to the side of
the building.
|
| |
11. |
All outside supply tanks shall be held to the same standards
as newly installed tanks.
|
| |
12. |
For a single-tank installation, the fuel supply line cannot
extend more than twelve (12) inches beyond the face of the tank.
|
| |
|